Overvoltage products Main power supplies
Transient overvoltages Modular cabinets - VE range - 120/208 V and 230/400 V~ networks Surge protective devices guideline (1)
The installation of the surge protective devices should be done in compliance with the electrical safety rules of the electrical standards NF C 15-100, IEC 60364 or all equivalent electrical standard in the country. As for all electrical equipments, their installation should be done according to the electrical safety rules, for the protection of the persons and equipments, against the risks of faults of the network and the directs or indirect contacts, coordination and of selectivity of the protection devices for the protection against the heating and fires risks, types of protection devices specified in the technical sheets of the SPD `s.

According to the risk assessment
Risk assessment (methodology: refer also the practical guide) HVLV downstream protection2 Main Board Divisionary board Equipments at more than 30 m3 Secondary buildings (main boards) Risk assessment (methodology: refer also the practical guide) HVLV downstream protection Main Board Divisionary board Equipments at more than 30 m Secondary buildings (main boards)
3 2

Level of risk WITH lightning conductor1 Very high (R1) T1-25 T2-60 T2-40 T1-12.5 T1-25 T1-12.5 T2-60 T2-40 T1-12.5 T1-12.5 T2-40 T2-10 T1-12.5 High (R2) T1-25 T1-12.5 T2-40 T2-10 4 T1-12.5 Medium (R3) T1-12.5 T2-40 T2-10 4 T1-12.5 Low (R4) T1-12.5 T2-40 T2-10 4 T1-12.5

Level of risk WITHOUT lightning conductor Very high (R1) T1-12.5 T2-60 T2-40 T2-60 T1-12.5 T2-60 T2-40 T2-10 T2-40 T2-60 T2-40 T2-10 4 T2-40 High (R2) T1-12.5 T2-40 T2-10 T2-10
4

Medium (R3) T2-40 T2-10 4 T2-10
4

Low (R4) T2-10 T2-10 4 T2-10 4 T2-10 4

T2-10

T2-10

According to the protection mode
Mode 5 "3+1" ("1+1") "3+0" "4+0" ("2+0") Type of connection 5 "C1" "C2" "C2" Protected conductors 3 (1) surge arrestors in between line and neutral (differential mode) 1 spark gap in between neutral and earth (common mode) 3 surge arrestors in between line and earth (common mode) 4 (2) surge arrestors in between active cables (live and neutral) and the earth (common mode)

According to the risk assessment
Range TT system TNS system TNC system IT system IT+N system T1-25 (Iimp = 25 kA) ASS3114A1 ASS3114A1 ASS3312T1, x3 ASS1106C1, x3 ASS1118A1, x2 Protections recommended for three phases networks 230/400 V WITH lightning conductors T2-40 T2-60 T1-12.5 T2-10 (Imax = 40 kA) (Imax = 60 kA) (Iimp = 12.5 kA) (Imax = 10 kA) ASS4212D2 ASS8212A2 ASS1114D1 ASS1104D2 ASS1112C1, x2 ASS1112C1, x1ASS1112L1, x1 ASS1106C1, x1ASS1106L1, x1 ASS1118A1 ASS8212A2 ASS8212B2 ASS8214B2 ASS8214A2 ASS4212A2 ASS4212B2 ASS4214B2 ASS4214A2 ASS1104D2 ASS1108A2

TT system: Recommendations for the electrical safety
A protection type "C1" ("4+0" or "2+0") will be obligatorily installed downstream from the differential circuit breaker (RCD) of the board in which is integrated in order to ensure the protection against the indirect contacts (currents of defects). A protection type "C2" ("3+1" or "1+1") will be installed as well upstream as downstream from the differential circuit breaker of the board. 1 Independently of the risk assessment, a protection type 1 with limp = 12.5 kA min. (class I of tests, EN 61643-11) is compulsory at the input of a protected building, (or belonging to a protected site) against the direct impact of the lightning (lightning conductor...). 2 Protections recommended for important industrial sites and sensitive sites. 3 Protections recommended when the equipment to protect are distant more than 30 m from the upstream protection (effects of lines which can provoke overvoltages superior to the residual tension of the surge protective device). 4 Optional. Protections recommended if the continuity of service is required or in presence of sensitive equipment. 5 2+0, 3+0, or 4+0 (type "C1"): protection L-PE and N-PE (connection of type 1) 3+1 or 1+1 (type "C2"): protection L-N and N-PE (connection type 2). L: line N: neutral PE: earth.

72

Dans la boutique



pdf Blunt Tip Lightning Rod
pdf Blunt Tip Lightning Rod
09/04/2011 - www.franklin-france.com
Lightning Conductors Lightning rods NF C 17-100, IEC 1024 AFA 0001 PF Simple lightning rod " Franklin " Blunt Tip Type Franklin lightning rod, which are blunt tip tapered, have a perfectly slender and attractive point. They exist in nickel/chromium-plate copper and stainless steel versions. They have a standard length of 2,4m and can be extended by the addition of treated steel and stainless steel elevation rods. These systems do not require guying and can be up to 7 or 8 m long. The tip of 2F...

pdf page 72
pdf page 72
09/04/2011 - www.franklin-france.com
Overvoltage products Main power supplies Transient overvoltages Modular cabinets - VE range - 120/208 V and 230/400 V~ networks Surge protective devices guideline (1) The installation of the surge protective devices should be done in compliance with the electrical safety rules of the electrical standards NF C 15-100, IEC 60364 or all equivalent electrical standard in the country. As for all electrical equipments, their installation should be done according to the electrical safety rules, for the...

pdf page 76
pdf page 76
09/04/2011 - www.franklin-france.com
Overvoltage products Main power supplies Transient overvoltages VE range Modular cabinets - 230/400 V~ networks Protection of an industrial site with a very high lightning risk level Example based on the same site with an IT+N earthing system (refer to previous diagram). Protection Protection type Network type SPD Backup protection Cabinet Dry contacts 1 HVLV transformer None Main Board (Bg.1)1 production, stocks, ... F protection T1-25 / IT+N system 230 / 400 V three phase ASS3314T1 (x4) ASS5125FU...

pdf page 47
pdf page 47
09/04/2011 - www.franklin-france.com
Produits foudre Mâts supports et fixations Mâts rallonges Franklin pour paratonnerres à tiges Les mâts rallonges Franklin, constitués d'éléments de 2 mètres, s'emboîtent par recouvrement évitant le boulonnage et le ruissellement de l'eau à l'intérieur, sources de corrosion prématurée. De très grandes résistances, il est possible d'associer 3 mâts sur trépied sans haubanage pour une vitesse du vent pouvant atteindre 160 km/h. Ils sont livrés avec les colliers d'attache des conducteurs....

pdf page 97
pdf page 97
09/04/2011 - www.franklin-france.com
Produits associés Systèmes de prévention Systèmes autonomes pour réseaux d'énergie Réseaux 230/400 V~ - Tout régime de neutre Coffrets de protection pour réseaux stratégiques Normes : CEI 61643-1/2002, EN 61643-11 (NF C 61-740), NF C 15-100, NF EN 60950, 50081-1 et 50082-1 Description Ces coffrets sont destinés à la protection des équipements très sensibles des réseaux stratégiques alimentés. Totalement autonomes, ils protègent les équipements par la déconnexion ultra rapide...
 


03/12/2024 - www.bettermann.de
Résumé en cours de création pour ce fichier PDF

Vtr Evo
Vtr Evo
25/07/2024 - www.vti.fr
FABRICATION FRANÇAISE DEPUIS 1983 VOLT'AIR EVOLUTION ® SYSTÈME DE VENTILATION BASSE PRESSION vti.fr Le VOLT'AIR EVOLUTION sommaire 2 La ventilation mécanique basse pression 3 Pourquoi ventiler ? 4 Comment ça marche ? 6 Unités de ventilation basse pression 8 Bouches d'extraction 9 Entrées d'air 10 Accessoires et options

Doblo - Sanijura
Doblo - Sanijura
27/08/2019 - www.sanijura.fr
B C A Hors volumes Volume 3 IP X1 Volume 3 Volume 2 Volume 1 IP X4 IP X4 2,40 m 2,25 m 2,25 m 3m IP X1 0,60 m Volume 0 IP X7 Fitting instructions are intended to ease fitting.They are not subject to contract. Unverbindliche Montageanleitung. Deze montagehandleiding is bedoeld om de montage te vereenvoudigen. Zij is niet bindend. Le seguenti istruzioni sono destinate a facilitarvi il montaggio del mobile, e sono indicative. Since the type of wall determines the fittings necessary for...

Energy Label EES 80 G
Energy Label EES 80 G
19/06/2024 - aosmithinternational.com
A.O. Smith EES 80 XL 4430 15 0

NOTICE DUO 3000 - 047
NOTICE DUO 3000 - 047
10/03/2012 - kaufelfr.tnb.com
DUO 3000 DUO 3000 A DUO 3000 COM 1- PRESENTATION BAES d'évacuation à phares existant en version Standard, Autotestable SATI et Adressable SATI. Ces appareils sont homologués NF AEAS et sont conformes aux normes : · NF EN 60598-2-22 · NFC 71800 (déc 2000) · NFC 71820 (juil 99 - SATI) Technologie Standard SATI Adressable Désignation DUO 3000 DUO 3000 A DUO 3000 COM Référence 225 305 226 207 227 308 Licence T06023 T06022 T06021 * Les certificats d'homologation sont disponibles sur notre...

Fiche de Données de Sécurité - DAW France
Fiche de Données de Sécurité - DAW France
13/04/2018 - www.daw.fr
CAPAROL FRANCE Fiche de Données de Sécurité élaborée conformément à la directive 91/155/CEE Produit : DUPA-INN Date d'édition : 12 avril 2001 Dernière modification : 28 avril 2000 1. Identification du produit et de la société Nom du produit : DUPA-INN Fournisseur : CAPAROL FRANCE Adresse : 5 Rue des Clomarts - 77130 MONTEREAU Téléphone : 01 60 73 56 56 Télécopie : 01 60 73 56 59 Appel d'urgence : 01 45 42 59 59 2. Composition/informations sur les composants Caractérisation...