Technical data www.casambi.com
CBU-DCS
Installation
CBU-DCS draws its operating power directly from the DALI bus. For this reason, it is important to make sure that the DALI bus is externally powered. If CBU-DCS is connected directly to a DALI sensor or a DALI driver, these products must have an integrated DALI bus power supply. CBU-DCS draws 5 mA in idle mode with 30 mA peak current from the DALI bus.
Bluetooth controllable DALI controller
Use 0,5-1,5 mm2 solid or stranded conductor electrical wires. Strip the wire 6-8 mm from the end. Using wire ferrules is not recommended. Press the buttons on top of the dimmer case and insert the wires into the corresponding holes. The polarity of DA1 and DA2 does not matter.
CBU-DCS has two sets of connectors. These connectors are internally connected in parallel with each other. This way the DALI bus can be routed through the product for easy installation.
CBU-DCS, as any other Casambi product, should not be placed in a metal enclosure or next to large metal structures. Metal will effectively block radio signals which are crucial to the operation of the product. A thorough connectivity testing is strongly recommended in the installation site.
Description
Range
CBU-DCS is a Bluetooth controllable, Casambi enabled DALI controller. CBU-DCS does not have its own power supply. Instead, it is powered directly from a DALI bus.
Up to
30 m 1)
CBU-DCS can be controlled with Casambi app which can be downloaded free of charge from
Apple App Store and Google Play Store.
Wiring diagram, sensor
Operating conditions
Ambient temperature, ta:
-20...+55°C
Max. case temperature, tc:
+65°C
Storage temperature: -25...+75°C
Max. relative humidity:
0...80%, non-cond.
Connectors
Wire range, solid & stranded:
0,5 - 1,5 mm2