Pineville, NC 28134-7455
Reference: Laboratory Test Report
Lab Identification No. 55950
Invoice No. 87265
Dear Mr. Laffoday:
One (1) sample, identified as KVADRAT INC. SAHCO MOSS color: 0006 TREATED WITH
FLAMECOAT, was received and tested in accordance with the California Technical Bulletin 117-2013,
Section 1, Cover Fabric Test. The results are as follows:
Test Results
Vertical Char Lengths
14mm
14mm
14mm
The sample submitted meets the requirements of the above standard. There were no ignitions or smoldering after 45 minutes on any of the three specimens tested. In addition, none of the three test specimens displayed a char which was greater than 45 mm.