Overvoltage products Main power supplies
Transient overvoltages Modular cabinets - VE range - 120/208 V and 230/400 V~ networks Surge protective devices guideline (1)
The installation of the surge protective devices should be done in compliance with the electrical safety rules of the electrical standards NF C 15-100, IEC 60364 or all equivalent electrical standard in the country. As for all electrical equipments, their installation should be done according to the electrical safety rules, for the protection of the persons and equipments, against the risks of faults of the network and the directs or indirect contacts, coordination and of selectivity of the protection devices for the protection against the heating and fires risks, types of protection devices specified in the technical sheets of the SPD `s.

According to the risk assessment
Risk assessment (methodology: refer also the practical guide) HVLV downstream protection2 Main Board Divisionary board Equipments at more than 30 m3 Secondary buildings (main boards) Risk assessment (methodology: refer also the practical guide) HVLV downstream protection Main Board Divisionary board Equipments at more than 30 m Secondary buildings (main boards)
3 2

Level of risk WITH lightning conductor1 Very high (R1) T1-25 T2-60 T2-40 T1-12.5 T1-25 T1-12.5 T2-60 T2-40 T1-12.5 T1-12.5 T2-40 T2-10 T1-12.5 High (R2) T1-25 T1-12.5 T2-40 T2-10 4 T1-12.5 Medium (R3) T1-12.5 T2-40 T2-10 4 T1-12.5 Low (R4) T1-12.5 T2-40 T2-10 4 T1-12.5

Level of risk WITHOUT lightning conductor Very high (R1) T1-12.5 T2-60 T2-40 T2-60 T1-12.5 T2-60 T2-40 T2-10 T2-40 T2-60 T2-40 T2-10 4 T2-40 High (R2) T1-12.5 T2-40 T2-10 T2-10
4

Medium (R3) T2-40 T2-10 4 T2-10
4

Low (R4) T2-10 T2-10 4 T2-10 4 T2-10 4

T2-10

T2-10

According to the protection mode
Mode 5 "3+1" ("1+1") "3+0" "4+0" ("2+0") Type of connection 5 "C1" "C2" "C2" Protected conductors 3 (1) surge arrestors in between line and neutral (differential mode) 1 spark gap in between neutral and earth (common mode) 3 surge arrestors in between line and earth (common mode) 4 (2) surge arrestors in between active cables (live and neutral) and the earth (common mode)

According to the risk assessment
Range TT system TNS system TNC system IT system IT+N system T1-25 (Iimp = 25 kA) ASS3114A1 ASS3114A1 ASS3312T1, x3 ASS1106C1, x3 ASS1118A1, x2 Protections recommended for three phases networks 230/400 V WITH lightning conductors T2-40 T2-60 T1-12.5 T2-10 (Imax = 40 kA) (Imax = 60 kA) (Iimp = 12.5 kA) (Imax = 10 kA) ASS4212D2 ASS8212A2 ASS1114D1 ASS1104D2 ASS1112C1, x2 ASS1112C1, x1ASS1112L1, x1 ASS1106C1, x1ASS1106L1, x1 ASS1118A1 ASS8212A2 ASS8212B2 ASS8214B2 ASS8214A2 ASS4212A2 ASS4212B2 ASS4214B2 ASS4214A2 ASS1104D2 ASS1108A2

TT system: Recommendations for the electrical safety
A protection type "C1" ("4+0" or "2+0") will be obligatorily installed downstream from the differential circuit breaker (RCD) of the board in which is integrated in order to ensure the protection against the indirect contacts (currents of defects). A protection type "C2" ("3+1" or "1+1") will be installed as well upstream as downstream from the differential circuit breaker of the board. 1 Independently of the risk assessment, a protection type 1 with limp = 12.5 kA min. (class I of tests, EN 61643-11) is compulsory at the input of a protected building, (or belonging to a protected site) against the direct impact of the lightning (lightning conductor...). 2 Protections recommended for important industrial sites and sensitive sites. 3 Protections recommended when the equipment to protect are distant more than 30 m from the upstream protection (effects of lines which can provoke overvoltages superior to the residual tension of the surge protective device). 4 Optional. Protections recommended if the continuity of service is required or in presence of sensitive equipment. 5 2+0, 3+0, or 4+0 (type "C1"): protection L-PE and N-PE (connection of type 1) 3+1 or 1+1 (type "C2"): protection L-N and N-PE (connection type 2). L: line N: neutral PE: earth.

72

Dans la boutique



pdf page 72
pdf page 72
09/04/2011 - www.franklin-france.com
Overvoltage products Main power supplies Transient overvoltages Modular cabinets - VE range - 120/208 V and 230/400 V~ networks Surge protective devices guideline (1) The installation of the surge protective devices should be done in compliance with the electrical safety rules of the electrical standards NF C 15-100, IEC 60364 or all equivalent electrical standard in the country. As for all electrical equipments, their installation should be done according to the electrical safety rules, for the...

pdf page 97
pdf page 97
09/04/2011 - www.franklin-france.com
Produits associés Systèmes de prévention Systèmes autonomes pour réseaux d'énergie Réseaux 230/400 V~ - Tout régime de neutre Coffrets de protection pour réseaux stratégiques Normes : CEI 61643-1/2002, EN 61643-11 (NF C 61-740), NF C 15-100, NF EN 60950, 50081-1 et 50082-1 Description Ces coffrets sont destinés à la protection des équipements très sensibles des réseaux stratégiques alimentés. Totalement autonomes, ils protègent les équipements par la déconnexion ultra rapide...

pdf Blunt Tip Lightning Rod
pdf Blunt Tip Lightning Rod
09/04/2011 - www.franklin-france.com
Lightning Conductors Lightning rods NF C 17-100, IEC 1024 AFA 0001 PF Simple lightning rod " Franklin " Blunt Tip Type Franklin lightning rod, which are blunt tip tapered, have a perfectly slender and attractive point. They exist in nickel/chromium-plate copper and stainless steel versions. They have a standard length of 2,4m and can be extended by the addition of treated steel and stainless steel elevation rods. These systems do not require guying and can be up to 7 or 8 m long. The tip of 2F...

pdf page 76
pdf page 76
09/04/2011 - www.franklin-france.com
Overvoltage products Main power supplies Transient overvoltages VE range Modular cabinets - 230/400 V~ networks Protection of an industrial site with a very high lightning risk level Example based on the same site with an IT+N earthing system (refer to previous diagram). Protection Protection type Network type SPD Backup protection Cabinet Dry contacts 1 HVLV transformer None Main Board (Bg.1)1 production, stocks, ... F protection T1-25 / IT+N system 230 / 400 V three phase ASS3314T1 (x4) ASS5125FU...

pdf page 47
pdf page 47
09/04/2011 - www.franklin-france.com
Produits foudre Mâts supports et fixations Mâts rallonges Franklin pour paratonnerres à tiges Les mâts rallonges Franklin, constitués d'éléments de 2 mètres, s'emboîtent par recouvrement évitant le boulonnage et le ruissellement de l'eau à l'intérieur, sources de corrosion prématurée. De très grandes résistances, il est possible d'associer 3 mâts sur trépied sans haubanage pour une vitesse du vent pouvant atteindre 160 km/h. Ils sont livrés avec les colliers d'attache des conducteurs....
 


28/09/2024 - www.vescom.com
Résumé en cours de création pour ce fichier PDF


08/11/2024 - www.rheinzink.fr
Résumé en cours de création pour ce fichier PDF


08/11/2024 - www.rheinzink.fr
Résumé en cours de création pour ce fichier PDF

aluform prospekt beschichtung antitropf
aluform prospekt beschichtung antitropf
09/04/2011 - www.aluform.de
PRODUKTE AntitropfBeschichtung flexible building. sustainable thinking. PRODUKTE Antitropf-Beschichtung GRAFO-THERM beschichtete Aluminium-Profiltafeln für Dach- und Fassadenkonstruktionen Bei bestimmten raumklimatischen Bedingungen besteht in Abhängigkeit von den Außentemperaturen bei Dächern aus Aluminium-Profiltafeln ohne Wärmedämmung (Kaltdächer) die Gefahr von Kondensatbildung. Die Kondensatbildung ist darauf zurückzuführen, dass sich die wärmere und wasserdampfhaltigere Innenluft...

Nomination : Fabrice Véront devient Directeur Général de Picard Serrures
Nomination : Fabrice Véront devient Directeur Général de Picard Serrures
22/05/2023 - www.andresudrie.com
Information Presse Mai 2023 Nomination : Fabrice Veront devient Directeur General de Picard Serrures Depuis le 1er Mars 2023, Fabrice Veront, 55 ans, a ete nomme Directeur General de Picard Serrures, fabricant francais de serrures de haute securite certifiees, de portes blindees surmesure, portes de hall et portes techniques. Il succede ainsi a Thierry Delaume qui, apres 6 ans au sein de l'entreprise, a fait valoir ses droits a la retraite. Titulaire d'un diplome d'ingenieur Arts & Metiers en Productique,...

SO!night by Soprofen : plus de lumière en journée et une meilleure occultation la nuit : le rêve d'un sommeil de qualité devient enfin réalité !
SO!night by Soprofen : plus de lumière en journée et une meilleure occultation la nuit : le rêve d'un sommeil de qualité devient enfin réalité !
09/09/2020 - www.andresudrie.com
INFORMATION PRESSE SEPTEMBRE 2020 BY SOPROFEN PLUS DE LUMIERE EN JOURNEE ET UNE MEILLEURE OCCULTATION LA NUIT : LE REVE D'UN SOMMEIL DE QUALITE DEVIENT ENFIN REALITE ! En France, pres de 20% de la population souffre d'insomnie*. Parmi les principaux ennemis du sommeil figurent le bruit et la lumiere. De plus en plus, l'organisme humain est sollicite par la pollution sonore et lumineuse. Des lors, il devient difficile de preserver un environnement nocturne propice a un sommeil de qualite. Pour...